Signa Product
Producta nostra stricte conficiuntur secundum signa nationalia et internationalia. Customisatio secundum certas necessitates internationales etiam in promptu est:
National Standard: GB/T 5023-2008 (PVC funiculos insulatos de voltages aestimatos usque ad 450/750V comprehendo).
Industry Standard: JB/T 8734-2016 (PVC funiculos, filis insulatas, plicas flexibiles voltages aestimatos usque ad et inclusos 450/750V).
International Compatibility: Productio formari potest obviam IEC, BS, DIN et signa ICEA.
Features structurales et materiales
Nos prioritizamus summus qualitas materiae rudis et subtilitas machinalis ad invigilandum producti integritatis;
Summus Puritas Conductor: premium aeris electrical-gradus annealed (vel aluminium), offerens maximum DC resistentiam, et conductivity superior ad minuendum energiae detrimentum in transmissione.
Magnum Insulation: Core inclusum est in summo opere Polyvinyl Chloride (PVC), optimum resistentiam acidis, alcali, oleis et umoribus praebens.
Optimized structuralis integritas: Nam rudentes multi-nuclei vel circumfusae, scientifice formatae filler materiae et machinae ligaturae speciales adhibitae sunt ad rotunditatem funes et vires mechanicas ut altiorem tutelam augendae.
Operating Characteres & euismod Commoda
Multi-Level Resistentia Scelerisque: Maximum continuum temperamentum operans conductor est typice 70°C. Pro postulatione applicationum, exempla specifica IEC (exampla, 60227 IEC 07/08) ambitus usque ad 90°C sustinere possunt.
Superior flexibilitas flexibilitas: funes praestantem mechanicam duritiam exhibent. Nam retinae cum diametro exteriore 25mm vel minore, radius curvus tam parvus esse potest quam 4D; pro diametris majoribus (D> 25mm), semidiameter conservatur ad 6D, quo faciliorem reddat institutionem efficientem in spatiis complexis.
Adaptabilitas environmentalis: Cables directe in temperaturis ambientibus institui non possunt minus quam 0°C sine praecalefactione, efficiendi efficaciam praestandi etiam in climatibus provocandis.
Caput Applications
Hoc productum range versatile ordinatur ad praecisionem wiring necessitates occurrendas per varias missiones;
Potestas System Wiring: Praesertim ad certam institutionem systematum potestatum adhibita intentione aestimata 450/750V et infra.
Aedificatio et Industrialis Fixarum Wiring: Apta nexus internis in aedificiis, scriniis control et switchgear.
Connexio flexibilis missionum: In specie designatae solutiones funiculi flexibiles (exempli gratia, RVV, RV) praesto sunt ad adjumenta electrica frequentes motus vel flexiones requirentes.
Typus et nomen funis
| Type | Nomen | Signa |
| 60227 IEC 01(BV) | Una-core non vaginatae funem solido conductor ad proposita communia | |
| 60227 IEC 02(RV) | Single-core non-calatum funem flexibili conductor ad proposita communia | GB/T 5023-2008 IEC60227 |
| 60227 IEC 05(BV) | Uno-core non vaginato funem solidum conductor pro wiring interna pro a conductor temperatus 70℃ |
| 60227 IEC 06(RV) | Unius nucleus non-rete vaginatus cum solidis flexilibus conductor pro internis wiring ad conductorem temperatus ex 70℃ |
| 60227 IEC 07(BV-90) | Uno-core non vaginato funem solido conductor pro interna wiring ad conductorem temperatus est 90℃ |
| 60227 IEC 08(RV-90) | Unius coro non-rete vaginatis funem conductor flexibili ad internum wiring ad conductorem temperatus est 90℃ |
| 60227 IEC 10(BVV) ; ; | Lux PVC vaginatus funem |
| 60227 IEC 52(RVV) | Lux PVC funiculus flexibilis vaginatus |
| 60227 IEC 53(RVV) | Ordinarius PVC funiculus flexibilis vaginatus |
| 60227 IEC 56(RVV-90) | Conductor temperatus ad 90℃ordinarius calor resistens PVC vaginalis filum flexibile |
| 60227 IEC 57(RVV-90) | Conductor temperatus 90℃ ordinarius ignis redardantis PVC vaginalis filum flexibile |
| 60227 IEC 74(RVVYP) | Oleum probatum PVC vaginatum, funem texit |
| 60227 IEC 75(RVVY) | Oleum probatum PVC vaginatum, funem flexibilem non obiectu |
| BV | Aeris conductor PVC insulatas filum | JB/T 8734-2016 |
| BLV | Aluminium conductor filum PVC insulatas |
| BVR | Aeris conductor PVC insulatas funem flexibile |
| BVV | Aeris conductor PVC insulatas et circumtetas funem |
| BLVV | Aluminium conductor PVC insulatas et circumtetas funem |
| BVVB | Aeris conductor PVC insulatas et circumfusas plana funem |
| BLVVB | Aluminium conductor PVC insulatas et fundatas funem |
| RVS | Aeris conductor PVC insulatas torta flexilis spinalis pro nexu |
| RVB | Aeris conductor PVC insulatas planas destrinxit flexibile funem |
| RVP | Aeris conductor PVC insulatas vaginatus funiculus flexibilis |
| RVP-90 | Aeris conductor PVC insulatas texit flexibile funiculum pro conductor temperatus est 90℃ |
| RVV | PVC insulatas PVC-vatas retinacula flexibilis |
| RVVP | Aeris conductor PVC insulatas et circumfusas texit flexibiles funes |
Productio Teli cable
| Type | Rated voltage | No.of metretas | Nominalem crucem-sectionalem conductoris mm² | Signa |
| 60227 IEC01(BV) | 450/750 | 1 | 1.5~400 | GB/T 5203-2008 IEC60227 |
| 60227 IEC 02(RV) | 450/750 | 1 | 1.5~240 |
| 60227 IEC 05(BV) | 300/500 | 1 | 0.5~1 |
| 60227 IEC 06(RV) | 300/500 | 1 | 0.5~1 |
| 60227 IEC 07(BV-90) | 300/500 | 1 | 0.5~2.5 |
| 60227 IEC 08(RV-90) | 300/50 | 1 | 0.5~2.5 |
| 60227 IEC 10(BVV) ; ; | 300/500 | 2,3,4,5 | 1.5~35 |
| 60227 IEC 52(RVV) | 300/300 | 23 | 0.5~0.75 |
| 60227 IEC 53(RVV) | 300/500 | 2,3~24 | 0.75~6 |
| 60227 IEC 56(RVV-90) | 300/300 | 23 | 0.5~0.75 |
| 60227 IEC 57(RVV-90) | 300/500 | 2,3,4,5 | 0.75~2.5 |
| 60227 IEC74(RVVYP) | 300/500 | 2~60² | 0.5~2.5 |
| 60227 IEC75(RVVY) | 300/500 | 2~60² | 0.5~2.5 |
| BV | 300/500 | 1 | 0.75~1 | JB/T8734-2016 |
| BLV | 450/750 | 1 | 2.5~630 |
| BVR | 450/750 | 1 | 2.5~ 240 |
| BVV | 300/500 | 1 | 0.75~185 |
| BLVV | 300/500 | 1 | 2.5~ 185 |
| BVVB | 300/500 | 2,3 | 0.75~10 |
| BLVVB | 300/500 | 2,3 | 2.5~10 |
| RVS | 300/300 | 2 | 0.5~0.6 |
| RVB | 300/300 | 2 | 0.5~0.6 |
| RVP、RVP-90 | 300/300 | 12 | 0.08~6 |
| RVV | 300/500 | 2~41 | 0.5~10 |
| RVVP | 300/300 | 1,2~24" | 0.3~6 |
| 1) Numerus nucleorum: 4,5,6,7,10,12,14,16,19 et 24; 2) Numerus nucleorum: 2,3,5,4,5,6,7,12,18,27,36,48 et 60. Nota: Species speciales ignis retardantis, resistentis flammei, fumi humilis et halogeni, fumi et non halogani nec non acidi alkali-probationis pro his schedulis suppleri possunt. |
Current-portandi capacitatem PVC insulatas funem fixum posuit
| Type | 60227 IEC01(BV) 60227 IEC 02(RV) 60227 IEC 05(BV) 60227 IEC 06(RV) |
| Voltage | 450/750V |
| No. de metretas | Siugle core |
| Ordinatio | 1) | 1) | 1) | 2) |
| Conductor sectionis area (mm²) | A | A | A | A |
| 0.5 | 7 | 9 | 7 | 11 |
| 0.75 | 9 | 12 | 9 | 14 |
| 1.0 | 11 | 14 | 11 | 16 |
| 1.5 | 14 | 18 | 14 | 21 |
| 2.5 | 19 | 25 | 20 | 29 |
| 4 | 26 | 33 | 27 | 38 |
| 6 | 33 | 42 | 34 | 49 |
| 10 | 48 | 58 | 49 | 68 |
| 16 | 65 | 78 | 67 | 91 |
| 25 | 89 | 105 | 91 | 120 |
| 35 | 110 | 130 | 110 | 150 |
| 50 | 135 | 155 | 140 | 180 |
| 70 | 175 | 200 | 180 | 230 |
| 95 | 220 | 250 | 225 | 290 |
| 120 | 255 | 290 | 265 | 335 |
| 150 | 295 | 335 | 305 | 390 |
| 185 | 345 | 390 | 360 | 450 |
| 240 | 420 | 470 | 435 | 545 |
| 300 | 490 | 540 | 505 | 630 |
| 400 | 575 | 635 | 595 | 735 |
| operating temperatus | 70(℃) |
| Ambiens temperatus | 40(℃) |
Nota:
(I) mutua contactu retinacula
(2) Centrum intervallum funibus adjacentium est 2 temporibus diametri funis
Ambiens conditio
Fixum in aere: environment temperatus: vile in aere 40℃
Cum temperatura a fiduciali temperatura in chartula capacitatis hodiernae differet, coefficientes remediales sic enumerantur.
Charta coefficiens currentis-portandi facultatem cum temperatura differt
| operating temperatus of conductor | Aiibient tenperaturrc (℃) |
| 20 | 25 | 30 | 35 | 40 | 45 | 50 | 55 |
| 60 | 1.52 | 1.40 | 1.28 | 1.15 | 1.00 | 0.84 | 0.66 | 0.43 |
| 70 | 1.36 | 1.28 | 1.19 | 1.10 | 1.00 | 0.90 | 0.78 | 0.66 |
| 75 | 1.30 | 1.23 | 1.16 | 1.08 | 1.00 | 0.91 | 0.82 | 0.73 |
| 90 | 1.23 | 1.17 | 1.12 | 1.06 | 1.00 | 0.94 | 0.87 | 0.81 |